SURGEX SEQ1U Overview

The 1U, 120V/20A Programmable Sequencer Surge Eliminator from SurgeX allows sequencing of various types of electronic equipment that need to be powered up or down in order, rather than simultaneously. In AV systems, sequencing is often necessary for controlling the distribution of power to avoid equipment damage. This sequencer provides the sequencing parameters, conditioning, shutdown thresholds, and surge protection needed to safeguard audio, video, broadcast, and computer equipment. This unit has robust management features and is extremely easy to install, program, and use. It includes 2 always-on receptacles and 4 programmable banks. The SEQ features one virtual bank for controlling remote units, allowing for infinitely expanding distribution schemes. The SEQ also includes an LCD screen on the front panel that provides unit status, AC line voltage, and is also used in programming the unit. Settings are saved in nonvolatile memory. The SEQ can control other SurgeX products, or several SEQs can be interconnected to operate together. With many powerful features, the SEQ is extremely easy to install, program and use.

This surge elliminator is engineered with Advanced Series Mode surge elimination technology to provide top-of-the-line protection. Completely non-sacrificial and never needing reset, they provide reliable protection and eliminate surge energy up to 6,000V without producing harmful side effects such as ground contamination or common-mode disturbances. The SEQ Sequencer also features both common mode and normal mode impedance tolerant EMI/RFI filtering, SurgeX ICE (Inrush current elimination), and CouVS (Catastrophic over/under Voltage shutdown) for a complete power conditioning solution.

  • Advanced Series Mode surge protection
  • Three sequenced banks of 4 receptacles; two always-on receptacles
  • Setup stored in nonvolatile memory
  • Advanced Impedance Tolerant EMI/RFI filtering
  • Over/under voltage shutdown
  • SurgeX ICE inrush current elimination technology
  • Can be used to control other SurgeX products or daisy-chained with other SEQ sequencers
  • LCD screen
  • Magnetic shielding steel enclosure
  • 9' (2.75m) grounded 3-wire #12 line cord
  • Provides continual display of AC line voltage
  • Accommodates any type of control input
  • DC voltage or contact closure feedback to Crestron, AMX, or similar control devices
  • Output to drive up to four status LEDs
  • Advanced Series Mode surge protection
  • COUVS catastrophic over/under-voltage shutdown
  • Thermal circuit breaker overload protection
  • Made in USA

SURGEX SEQ1USpecs

Load Rating
20 A @ 120 V
Certifications & Approvals
UL 1449 Adjunct Classification Test Results: 1,000 surges, 6,000 V, 3,000 A, B3 pulse
Measured suppressed voltage: 170 V, no failures
Federal Guidelines: Grade A, Class 1, Mode 1 (CID A-A-55818)
EMI/RFI Filter, Normal Mode (50 Ω load): > 30 dB at 100 KHz to 50 MHz
EMI/RFI Filter, Common Mode (50 Ω load): > 20 dB (1 to 50 MHz)
Under-Voltage Auto Shutdown: Adjustable from 90 to 110 V
Over-Voltage Auto Shutdown: Adjustable from 130 to 150 V
Safety
Surge Let-Through Voltage (6,000 V surge): 0 V
Maximum Applied Surge Voltage: 6,000 V
Maximum Applied Surge Current: Unlimited, due to current limiting
Maximum Applied Surge Energy: Unlimited, due to current limiting
Endurance (C62.41-1991 Category B3 pulses): 1 kV > 500,000, 3 kV > 10,000, 6 kV > 1,000
Maximum Load Inrush Energy: 1,400 Joules total during power-up
Control Input
Momentary Switch, Latching Switch, Contact Closure, or 5 to 30 VDC
Current
Input Control Current: 3 mA
Contact Closure Maximum Resistance: 40 mA
Output
DC: 12 VDC, 40 mA maximum load
Auxiliary Relay Contact Rating: 30 VDC at 1 A
Resistance
12 VDC Output Maximum Current: 100 Ω
Delay
1 to 40 seconds in 1 second increments
Temperature Range
41 to 95ºF (5 to 35ºC)
Humidity Range
5 to 95% R.H., non-condensing
Listings
UL 1449 3rd Edition (Pending), UL 1283 5th Edition (Pending), CSA C22.2 No.8-M1986 (R2008) (Pending)
Dimensions
1.75 x 19.0 x 12.25" (4.40 x 48.30 x 31.00 cm)
Weight
13.0 lb (5.9 kg)